ULTRAPOWER — Ultra Power Systems

High Voltage Programmable DC Power Supply: 1000 V to 2250 V

Choosing a high-voltage class is about matching your highest bus voltage with enough headroom, then sizing power and form factor. Here is how the 1000 V, 1500 V and 2250 V classes line up.

Pick the voltage class first

Voltage class is the gating decision. Run your supply at or just above the maximum bus voltage your device under test will ever see, with sensible headroom for transients. Under-specifying caps your test envelope; wildly over-specifying wastes resolution. The N35500 platform from Ultra Power Systems spans the full 0-2250 V range so you can match the class to the application rather than compromise.

Across every class the supply holds 0.02% F.S. accuracy and responds in ≤5 ms, and each is fully programmable with CC/CV/CP/CR modes.

Voltage-class buyer table

ClassVoltagePer-chassis powerForm factorTypical applications
1000 V0-1000 Vup to 42 kW3U, MW via parallelEV 400/800 V packs, OBC/BOBC, motor drive
1500 V0-1500 Vup to 42 kW3U, MW via parallelPV strings, ESS/PCS/BESS, utility inverters
2250 V0-2250 Vup to 42 kW3U, MW via parallelHV stacks, aerospace/ATE, research

All three classes share the 3U chassis and the same master/master paralleling, so the path from a single bench unit to a megawatt floor does not change the form factor logic, only the count of chassis.

Safety and compliance at high voltage

High-voltage work raises the stakes on isolation, interlocks and calibration. The platform is built to CE and IEC 61010, regenerates in line with IEEE 1547, and ships with ISO 17025-traceable calibration so your measurements stand up to audit. For PV emulation at high string voltages, the NS91000 option adds EN50530 static/dynamic and Sandia MPPT profiles.

Headroom, resolution and the cost of getting it wrong

It is tempting to buy the highest class "to be safe," but voltage class is a trade-off against resolution. A 2250 V unit set to test a 400 V device works the full range across a fraction of its span, so absolute resolution at your operating point is coarser than a unit matched to that bus. The right move is to choose the smallest class that still clears your maximum bus voltage plus a margin for transients and future devices.

The flip side, under-specifying, is worse: a class that cannot reach your bus voltage simply cannot run the test. Because all three classes share the same 42 kW/3U building block, accuracy figure and feature set, you lose nothing on capability by matching the class tightly, you only gain measurement resolution where it counts.

For high-voltage PV and string work, the platform also runs full array emulation at class voltage, so a 1500 V unit can replay realistic string I-V curves rather than just hold a fixed setpoint.

Specify your high-voltage system

Tell the manufacturer your maximum bus voltage, continuous and peak power, and whether you need PV or battery emulation at that class. The request-a-quote form captures this, or write to Ultra Power Systems. For the energy economics of high-power discharge, see the regenerative supply guide.

Frequently asked questions

What is the highest voltage available?
The N35500 platform reaches 0-2250 V. Lower classes at 1000 V and 1500 V cover EV traction buses and PV/ESS strings respectively.
Does higher voltage mean lower power or a bigger chassis?
No. All voltage classes deliver up to 42 kW in the same 3U chassis, and all scale to megawatt levels via master/master paralleling.
Is the calibration traceable for high-voltage measurements?
Yes. Calibration is ISO 17025-traceable, and the units meet CE and IEC 61010, so high-voltage results are defensible in audited environments.

Get a configured quote

Tell us your voltage, power, application and timeline and get a configured quote from Ultra Power Systems.

Get a Quote Contact the team